Toronto Data Centre 6
Technical Specifications
| BUILDING DESCRIPTION | |
| Building size | 200,000 SF |
| Utility power | Alectra, 27,600 volts |
| Parking | Surface parking |
| Number of storeys | 2 |
| Loading docks | 3 indoor with dock levellers |
| COMPUTER ROOM SPECIFICATIONS | |
| Available rooms | Multiple |
| Standard critical power | 3 MW – 6MW per data hall |
| High density ready | Yes |
| Approximate size | 10,000 SF for IT equipment |
| COMPUTER ROOM DENSITY | |
| Standard density | 10-50 kW per rack |
| Optional density | 125+ kW per rack |
| COMPUTER ROOM DESCRIPTION | |
| Computer rooms | Dedicated |
| Floor height | Slab on grade, minimum 18’ building height |
| Floor to ceiling height | open to structure |
| Floor loading | 200+ pounds per square foot |
| SECURITY | |
| Building and perimeter | Security check point for all access, ballistic glass and walls |
| Security guards | Yes, 7x24x365 |
| Access control | Yes, electronic access with dual authentication, minimum 1 biometric reader |
| Video surveillance | Yes, 7x24x365 of all exterior and interior areas, minimum 30 days of archive |
| CRITICAL POWER | |
| Total megawatts | 35 MW |
| UPS SYSTEMS | |
| Description | High efficiency static UPS |
| Redundancy | N+1 |
| GENERATORS | |
| Description | 3 MW diesel generator |
| Redundancy | N+1 |
| ON SITE FUEL CAPACITY | |
| Storage tanks | Sub-base tanks |
| Fuel runtime | 48 hours minimum |
| HEAT REJECTION SYSTEMS | |
| Description | Distributed and Redundant Direct Evaporative Cooling systems dedicated per data hall. |
| Redundancy | N+1 |
| Efficiency | Annualized mechanical PUE of 1.25 or better |
| PDUs | |
| Description | 525/600 PDUs |
| Redundancy | 2N |
| COMMUNICATIONS | |
| POE | 2 separate network points of entry with diverse underground duct banks to metropolitan network |
| Conduits | Dedicated diverse conduits and risers to each data floor |
| Multiple carriers | Yes, data centre is carrier neutral |
| FIRE PROTECTION | |
| Description | Double interlocked pre-action dry type sprinkler system with VESDA throughout building |
| DESIGN PUE | |
| Description | 1.3 maximum |
| *Some specifications listed are optional. |