Technical Specifications
BUILDING DESCRIPTION | |
Building size | 94, 439 SF |
Utility power | Hydro Quebec, 13,800 volts / 27,000 volts |
Parking | Surface parking |
Number of stories | 1 plus mezzanine |
Loading docks | 2 indoor with dock levelers |
COMPUTER ROOM SPECIFICATIONS | |
Available rooms | Multiple |
Standard critical power | 3 MW per data hall |
High density ready | Yes |
Approximate size | 10, 000 SF for IT Equipment |
Maximum cabinet spaces | Variable 550 standard 24’W x 48”D or 330 standard 32”W x 48”D |
COMPUTER ROOM DENSITY | |
Standard density | 150 watts per square foot |
Optional density | 300 watts per square foot |
COMPUTER ROOM DESCRIPTION | |
Computer rooms | Dedicated |
Floor height | Slab on grade, 18’ building height |
Floor to ceiling height | Base design with drop ceiling 12’6” to 13’6” |
Floor loading | 200 pounds per square foot |
SECURITY | |
Building and perimeter | Security check point for all accesses, ballistic glass and walls |
Security guards | Yes, 24/7 365 days |
Access control | Yes, electronic access with dual authentication, mimimum 1 biometric reader |
Video surveillance | Yes, 7x24x365 of all exterior and interior areas, minimum 30 days of archive |
CRITICAL POWER | |
Total megawatts | 20 MW |
UPS SYSTEMS | |
Description | High efficiency static UPS |
Redundancy | N+1 or 2N as required |
GENERATORS | |
Description | 3 MW diesel generator |
Redundancy | N+1 or 2N as required |
ON SITE FUEL CAPACITY | |
Storage tanks | Sub-base tanks |
Fuel runtime | 24 hour minimum |
HEAT REJECTION SYSTEMS | |
Description | Distributed and Redundant KyotoCooling systems dedicated per data hall |
Redundancy | N+1 |
Efficiency | Annualized mechanical PUE of 1.1 or better |
Efficiency at utilization | Unaffected by critical load utilization |
PDUs | |
Description | 250 amp overhead busway, optional multiple 400 KVA PDUs, 480V primary, 400/230V secondary available |
Redundancy | 2N |
COMMUNICATIONS | |
POE | 2 separate network points of entry with diverse underground duct banks to metropolitan network |
Conduits | Dedicated diverse conduits and risers to each data hall |
Multiple carriers | Yes, data centre is carrier neutral |
FIRE PROTECTION | |
Description | Double interlocked pre-action dry type sprinkler system with VESDA throughout building |
DESIGN PUE | |
Description | Designed to be best in class with a PUE as low as 1.08 regardless of critical load utilization |