image
Toronto Data Centre 3

Technical Specifications

BUILDING DESCRIPTION

 

Building size

106, 960 SF

Utility power


Hydro Quebec, 13,800 volts / 27,000 volts

Parking

Surface parking

Number of stories

1 plus mezzanine

Loading docks

2 indoor with dock levellers

COMPUTER ROOM SPECIFICATIONS

 

Available rooms

Multiple

Standard critical power

3 MW per data hall

High density ready

Yes

Approximate size

10, 000 SF for IT Equipment

Maximum cabinet spaces

Variable 550 standard 24’W x 48”D or 330

standard 32”W x 48”D

COMPUTER ROOM DENSITY

 

Standard density

150 watts per square foot

Optional density

300 watts per square foot

COMPUTER ROOM DESCRIPTION

 

Computer rooms

Dedicated

Floor height

Slab on grade, 18’ building height

Floor to ceiling height

Base design with drop ceiling 12’6” to 13’6”

Floor loading

200 pounds per square foot

SECURITY

 

Building and perimeter

Security check point for all accesses, ballistic glass and walls

Security guards

Yes, 24/7 365 days

Access control

Yes, electronic access with dual authentication, minimum 1 biometric reader

Video surveillance

Yes, 7x24x365 of all exterior and interior areas, minimum 30 days of archive

CRITICAL POWER

 

Total megawatts

20 MW

UPS SYSTEMS

 

Description

High efficiency static UPS

Redundancy

N+1 or 2N as required

GENERATORS

 

Description

3 MW diesel generator

Redundancy

N+1 or 2N as required

ON SITE FUEL CAPACITY

 

Storage tanks

Sub-base tanks

Fuel runtime

24 hour minimum

HEAT REJECTION SYSTEMS

 

Description

Distributed and Redundant KyotoCooling systems dedicated per data hall

Redundancy

N+1

Efficiency

Annualized mechanical PUE of 1.1 or better

Efficiency at utilization

Unaffected by critical load utilization

PDUs

 

Description

250 amp overhead busway, optional multiple 400 KVA PDUs, 480V primary, 400/230V secondary available

Redundancy

2N

COMMUNICATIONS

 

POE

2 separate network points of entry with diverse underground duct banks to metropolitan network

Conduits

Dedicated diverse conduits and risers to each data hall

Multiple carriers

Yes, data centre is carrier neutral

FIRE PROTECTION

 

Description

Double interlocked pre-action dry type sprinkler system with VESDA throughout building

DESIGN PUE

 

Description

Designed to be best

in class with a PUE as low as 1.08 regardless of critical load utilization

Need Space?

Let's discuss

  • Head office
  • 750 Lake Shore Blvd East
  • Toronto, ON M4M 3M3