SAULT STE. MARIE, ON

Secure knowledge – A purpose built next generation data centre in Canada



SAULT STE. MARIE INNOVATION CENTE
SAULT STE. MARIE, ON


  • SITE
    Building size ~30,000 GFA
    Transportation Trans Canada Highway, Interstate 75, Sault Ste. Marie Airport, Chippewa County International Airport, Pellston Regional Airport
    Parking 19 spaces
    BUILDING DESCRIPTION
    Utility power SSMPUC, 600 volts
    Parking Surface parking
    Number of storeys 1
    Loading docks 1 with dock leveller
    COMPUTER ROOM SPECIFICATIONS
    Available rooms 4
    Standard critical power 500 KW per data hall
    High density ready Yes
    Approximate size 5,000 SF for IT equipment
    Maximum cabinet 200 standard 24”W x 48”D
    COMPUTER ROOM DENSITY
    Standard density 100 watts per square foot
    Optional density Up to 200 watts per square foot
    COMPUTER ROOM DESCRIPTION
    Computer rooms Dedicated
    Floor height Slab on grade, 18’ building height
    Floor to ceiling height Base design with drop ceiling 12’6” to 13’6”
    Floor loading 200+ pounds per square foot
    LEASABLE OFFICE SPACE
    Office Common
    Storage Common
    SECURITY
    Building and perimeter Security check point for all access, ballistic glass and walls
    Security guards Yes
    Access control Yes, electronic access with dual authentication, minimum 1 biometric reader
    Video surveillance Yes, 7x24x365 of all exterior and interior areas, minimum 30 days of archive
  • CRITICAL POWER
    Total megawatts 2 MW
    UPS SYSTEMS
    Description High efficiency static UPS
    Redundancy 2N
    GENERATORS
    Description 1 MW diesel generator
    Redundancy 2N
    ON SITE FUEL CAPACITY
    Storage tanks Sub-base tanks
    Fuel runtime 24 hours minimum
    HEAT REJECTION SYSTEMS
    Description Redundant KyotoCooling systems dedicated per data floor
    Redundancy 2N
    Efficiency Annualized PUE of 1.2 or better
    Efficiency at utilization Unaffected by critical load utilization
    PDUs
    Description 250 amp overhead busway, optional multiple 250 KVA PDUs, 480V primary, 400/230V secondary available
    Redundancy 2N
    COMMUNICATIONS
    POE 2 separate network points of entry with diverse underground duct banks to metropolitan network
    Conduits Dedicated diverse conduits and risers to each data floor
    Multiple carriers Yes, data centre is carrier neutral
    FIRE PROTECTION
    Description Double interlocked pre-action dry type sprinkler system with VESDA throughout building
    design pue
    DESIGN PUE
    Description Designed to be best in class with an annualized PUE of 1.2 or better regardless of critical load utilization



    *Some specifications listed are optional.

“Sault Ste. Marie is home to the Prince Wind Farm, one of the largest wind energy farms in Canada. The site’s 126 turbines can produce 189 megawatts of renewable energy, enough to power about 60,000 homes or roughly two cities the size of Sault Ste. Marie.”Sault Ste. Marie Economic Development Corporation